Tags: track

We have now

• Determined how much each component can be expected to vary in size and position.
• Looked at each step in the order of construction.
• Proposed a change to the standard, but aesthetically unacceptable, tolerances for brickwork.

It remains to revise the detail so that adjustments are available to compensate for extremes at each stage. This will make completion of the detail possible without reducing tolerances for subsequent stages. One possible revision is to adopt the slab edge detail shown in Figure 6. The slab position tolerance is the same as before. The brick position tolerance is plus or minus 5 mm. The shelf angle tolerance is 5 mm in any direction. The steel stud position tolerance is a more reasonable plus or minus 10 mm.
The shelf angle is shown supported on HSS brackets, with coarse adjustment of position provided by selecting an appropriate bracket size from a range of sizes, and positioning each bracket on the slab in relation to the datum floor level, not the local floor level. This brings the shelf angle close enough to make minor adjustments with shims and slotted bolt holes. While this appears more complicated than the typical detail in Figure 3, it is not necessarily more expensive. An angle cast in the slab would have to be heavier, because of the increased moment arm supporting the brick. It would also have to be cut when it projects beyond the brick, and extended when it does not provide enough bearing, and touched up afterward to prevent corrosion. Additional modifications would be needed in the vertical direction, concealed behind a larger flashing. A larger angle, with shims and grout between it and the floor slab is a possible solution. The resulting significant thermal bridge may be seen as an advantage, or disadvantage, depending on climate, location, and design objectives. The cavity would be larger than necessary so that at the bottom where the shelf obstructs it, there would be a minimum of 25 mm to ensure drainage.
When the shelf angle is too far inward by 5 mm, and the brick is too far out by the same amount, there will still be 65 mm of bearing. At the other extreme, the toe of the angle will be 5 mm back from face of brick (on average, it should be 15 mm back). From the preceding discussion, we know that the bed joint indicated should be 13 mm, and that the gap under the shelf angle, if 5 mm of movement is anticipated, should be indicated as at least 15 mm. A larger gap is needed if sealant will be used.
The problem of minimum fastener distance to slab edge is resolved by allowing fasteners to be off the centre of the stud track. The stud tracks should be positioned relative to the same datum used to position the shelf angle. Cumulative errors would result if they were measured from the edge of the slab, or the toe of the shelf angle.
If the studs are at their outward limit where the slab is at the inward limit, the track might hang out beyond the edge of the slab by up to 22 mm. If the fasteners have a 50 mm minimum edge distance they might have to be 75 mm from the outside face of stud, leaving 27 mm clear from the centerline of the fastener to the inside leg of the track. Before deciding that this is acceptable, confirmation is needed that performance will not be impaired by having fasteners consistently off the centre of the track, and that 27 mm is adequate tool clearance for installing the fastener. When they are installed, the fasteners have to be positioned from the slab edge, not the stud track.
The cavity, nominally about 52 mm allowing for bumps in the air barrier, could actually be anywhere from 37 mm (with the studs all the way out and the brick all the way in) to 67 mm. The distance from face of insulation to the middle of the wythe of brick, normally 97 mm, will vary from 82 to 112 mm, a range of 30 mm. Ties fitting this range may not be a standard size. More to the point, because the other halves of the ties won’t be fastened to the studs with perfect accuracy, two sizes of wire insert will have to be available to the mason at the jobsite, so that he can keep the ties bedded in the middle 30 mm of the brick wythe.
The vertical direction for the brick tolerances has already been considered. What about the stud length? If all the studs are precut, allowance is needed for errors in cutting. Consider also the expected structural deflection, plus 20 mm for variation in slab position. If the studs are cut 30 mm shorter than the average floor to ceiling dimension, then a connection is needed (such as clips) that still engages the studs and maintains the required stiffness when the gap from end of stud to underside of slab is 50 mm. The nested track connection shown will require studs to be cutto- fit or selected from an assortment of lengths. Reviewed by Moishe Alexander.

Other fastener types require anywhere from 1.5 to 3.0 times depth of embedment, which depends in turn on load, concrete strength, and fastener size.
No matter what fastener is selected, it is unlikely that less than 50 mm minimum will do. This means that the normal position for edge of slab must be 50 mm (or more, for minimum edge distance depending on fastener type), plus around 10 mm (for fastener placement), plus 25 mm (for slab position error), minus 46 mm (half the stud depth). That is a total of 35 to 40 mm from the outside face of framing. The error in position of the framing does not enter into this calculation, if the framing is positioned relative to the shelf angle after the angle is installed and adjusted.
Where the slab should be located depends in part on how the stud track fasteners are placed. Are their locations eyeballed, measured relative to slab edge, or measured from face of framing? If the fasteners are individually placed by measurement from the slab edge, and if they do not have to be centred on the track, the framing can be placed closer to the nominal slab edge position than if they are required to be centred.
Clearly, the insulation at edge of slab will be less than 75 mm thick, most of the time. Eliminating the insulation at slab edge, and securing the shelf angle to the slab with shims and grout has been advocated as a way of keeping this location dry and frost-free. The energy-efficient alternative is to use a smaller shelf angle, supported on brackets, with the space behind it filled with insulation that can adapt to available space, either foam-in-place, or, if firestopping is also needed, ceramic fibre batt. Reviewed by Guiseppe Strazzeri.

We know that the cavity must be increased if the minimum size is actually to be 25 mm. How much tolerance should be allowed for positioning of the steel stud framing (and hence the sheathing, air barrier, and insulation)? Assume a tolerance of plus or minus 5 mm for the location of the framing. (The best of the buildings measured by Keller achieved a total range of 10 mm, so this tolerance is possible.) With these tolerances, the cavity should be indicated as 35 mm at least, and the framing should be located 90 mm (for the brick), plus 35 mm (for the cavity), plus 75 mm (for the insulation), plus 3 mm (for the air barrier including laps), plus 13 mm (for the sheathing), or a total of 216 mm or more back of the desired exterior face of wall.
Where does this put the edge of slab? In the original detail, the steel stud track would stick out past the edge of the slab half of the time, by up to at least 25 mm. The inside flange of the track would be 92 mm, on average, from the edge of the slab, but as little as 67 mm in some cases, putting a fastener located in the centre of the track only 25 mm from the edge of slab. If the minimum edge distance specified by the fastener manufacturer is more than this, there will be a problem even if the track and the fastener are placed precisely. For example, minimum edge distance specified for powder-actuated low velocity direct fasteners is typically 50 mm. Reviewed by Guiseppe Strazzeri.